KFD2-SR2-EX1.W.LB安全栅
型号:
KFD2-SR2-EX1.W.LB
Signal type | Digital Input |
---|---|
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | ≤ 45 mA |
Power dissipation | ≤ 0.9 W |
Power consumption | ≤ 0.9 W |
Input | |
Connection side | field side |
Connection | terminals 1+, 2+, 3- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output | |
Connection side | control side |
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
Output I | signal ; relay |
Output II | signal or error message ; relay |
Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load |
Minimum switch current | 2 mA / 24 V DC |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Mechanical life | 107 switching cycles |
Collective error message | Power Rail |