KFD2-SL2-EX1.B安全栅
型号:
KFD2-SL2-EX1.B
Signal type | Digital Output |
---|---|
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 20 ... 30 V DC |
Power consumption | max. 1.7 W at 45 mA output current |
Input | |
Connection side | control side |
Connection | terminals 7, 8 |
Input current | approx. 3 mA at 24 V DC |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC |
Output | |
Connection side | field side |
Internal resistor | 272 Ω |
Current | ≤ 45 mA |
Voltage | ≥ 11.7 V |
Open loop voltage | min. 24 V |
Connection | terminals 1+, 2- or 3- |
Output rated operating current | 45 mA |
Output signal | These values are valid for the rated operating voltages from 20 ... 30 V DC. |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Galvanic isolation | |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Power supply/Output | reinforced insu |