MC3140-385-2+0 现货直发
型号:
MC3140-385-2+0
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 0.2 W for Uin = 24 V, Iout = 20 mA | |
Control circuit | ||
Connection | terminals 11+, 12-; 9+, 10-, 8- | |
Voltage | 0 ... 24 V | |
Current | 0 ... 20 mA , I < 35 mA | |
Field circuit | ||
Connection | terminals 1+, 2-; 4+, 5- | |
Voltage | for 4 V ≤ Uin ≤ 24 V: Uout ≥ Uin - (0.41 x Iin in mA) - 0.5 | |
Short-circuit current | ≤ 35 mA | |
Transmission range | voltage: 4 ... 20 V DC/0 ... 6 Vpp AC current: 1 ... 20 mA | |
Transfer characteristics | ||
Deviation | ||
After calibration | ≤ 3.5 mA current loss at 20 mA load current | |
Influence of ambient temperature | ± 20 µA / K | |
Rise time/fall time | ≤ 50 µs (load current ≥ 1 mA) | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |