KFD2-CRG2-Ex1.D 安全栅现货直发
型号:
KFD2-CRG2-Ex1.D
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 130 mA | |
Power dissipation | 2 W | |
Power consumption | 2.5 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | ≥ 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 Ω (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA; short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 253 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 Ω | |
Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) | |
Energized/De-energized delay | 0 ... 250 s , adjustable |