KFD2-RCI-EX1 安全栅现货直发
型号:
KFD2-RCI-EX1
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | < 35 mA | |
Power consumption | < 0.8 W | |
Input | ||
Connection side | control side | |
Connection | terminals 10+, 11- | |
Input current | 40 mA at 19 ... 30 V DC | |
Signal level | 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Power consumption | < 1.2 W | |
Operating mode | loop powered | |
Output | ||
Connection side | field side/control side | |
Connection | terminals 1+, 3- (terminals 1+, 2 for test loop) | |
Internal resistor | approx. 275 Ω | |
Current | ≤ 20.4 mA | |
Voltage | ≥ 13.5 V | |
Open loop voltage | > 16 V | |
Voltage | 1-signal: > 13.5 V | |
Current | 1-signal: 20.4 A 0-signal: 4.2 mA | |
Load | max. 650 Ω | |
Response time | < 40 ms input to output | |
Line fault detection | short circuit voltage < 1 V , open circuit voltage > 16 V | |
Output II | ||
Connection | terminal 7: source (-) or sink (+), terminal 8: source (+), terminal 9: sink (-) | |
Current | 11 mA (source or sink mode) | |
Voltage | 9 ... 30 V sink mode from external supply | |
Load | max. 650 Ω , source mode , for HART ≥ 230 Ω | |
Communication | pass-through of HART signal between input II and output |